-40%

NEW ACTION INSTRUMENTS Q520-0B06-U NEW IN BOX

$ 224.4

Availability: 100 in stock
  • Condition: New
  • Return shipping will be paid by: Buyer
  • Model: TWO-WIRE ISOLATING TRANSMITTER
  • Item must be returned within: 60 Days
  • MPN: Q520-0B06-U
  • Refund will be given as: Money Back
  • All returns accepted: Returns Accepted
  • Brand: ACTION INSTRUMENTS
  • Restocking Fee: No

    Description

    ***FREE SHIPPING***
    ITEM NEW NEVER USED NO BOX THAT'S WHY BEING SOLD AS IS. FOR ANY OTHER QUESTION ON INQUIRES PLEASE MESSAGE US. IF YOU NEED SOMETHING WE WILL BE HAPPY TO HELP
    MERRIMAC INDUSTRIAL SALES
    Specifications
    Input:
    Accepts two J, K or T Type thermocouples
    Burnout Detection:
    Upscale standard; Downscale, option B
    Cold Junction
    Compensation Error
    1
    o
    C typical, 0 to 80
    o
    C ambient;
    3
    o
    C typical, -40 to 0
    o
    C ambient
    Output Range:
    4-20mA
    Supply Voltage Range:
    12 to 35VDC, each channel
    Output Accuracy:
    < 0.1% of full-scale input (mV) typical,
    < 0.2% max. @23
    o
    C including
    linearity, repeatability and hysteresis (not including CJC error)
    Adjustability:
    Front accessed 10 turn pot.,
    + 5% of span for zero and span
    Stability:
    <0.025%/
    o
    C of full-scale max. for full-scale and zero
    ESD Susceptibility:
    Meets IEC 801-2 level 2 (4kV)
    Isolation:
    1800VDC or peak AC between input and output
    and channel to
    channel
    Response Time:
    100mSec typical (10 to 90%)
    Temperature:
    Operating: -40 to 80
    o
    C (-40 to 176
    o
    F)
    Storage: -40 to 80
    o
    C (-40 to 176
    o
    F)
    Humidity
    (non-condensing):
    Operating: 15 to 90% (@45
    o
    C)
    Wire Terminals:
    Socketed screw terminals for 12-22 AWG
    Weight:
    0.34 lbs
    Agency
    Approvals:
    CSA certified per standard C22.2 (File No. LR42272).
    UL recognized per standard UL508 (File No. E9977